Module 1 · Electrical foundations
First draft, for your review · about 3 hours
Recommended first
Nothing: this module can be the first. (recommended, not enforced)
What the learner will be able to do
- Explain voltage, current and resistance, and use Ohm's law to find one from the other two. (plc.m1.o1)
- Tell a series circuit from a parallel one, say what each does to current and voltage, and explain why switches in series make AND and in parallel make OR. (plc.m1.o2)
- Say where AC and DC are used in a control panel, such as 120 V AC control power, 24 V DC for PLC inputs and outputs, and three-phase power for motors. (plc.m1.o3)
- Describe safe working practice at a control panel, including the steps of lockout/tagout in order. (plc.m1.o4)
Topics
Voltage, current and resistance · Ohm's law · Series and parallel circuits · AC and DC · Electrical safety and lockout/tagout
About this module
A PLC is a computer that switches electricity. Its inputs read voltages from buttons and sensors, and its outputs turn on lights, relay coils and motor contactors. To program one well, and to find out why a machine has stopped, you need to know what that electricity is doing.
This module gives you the words and the few rules that the rest of PLC+ uses:
- Voltage, current and resistance, and Ohm's law, which links them.
- Series and parallel circuits, and how switches wired in series and in parallel become the AND and OR of ladder logic.
- AC and DC: which kind of power each part of a control panel uses, and why.
- Working safely: the hazards in a panel and the lockout/tagout steps that keep you safe while you work on a machine.
Each item has a Learn page and a few practice questions on its Exercise tab. The module check at the end asks questions on all four. No earlier module is needed: start here.
The items
Each item has four tabs in PLC+: Learn (the lesson below), Example (a machine running a working program), Exercise (the learner writes the program; PLC+ checks it) and Reference. Every item has a comment box under it.
- 1.1 Voltage, current and resistance
- 1.2 Series and parallel circuits
- 1.3 AC and DC in a control panel
- 1.4 Working safely: lockout/tagout
- 1.5 Module check
1.1 Voltage, current and resistance
about 30 minutes
- Example
- None: this item has no machine.
- Exercise
- Practice questions (below). Passing them completes the item.
- Reference
- Ohm's law and power
The Learn tab
Voltage, current and resistance
Electricity in a circuit is described by three quantities. Every later lesson uses them, so it is worth learning them well.
The three quantities
- Voltage is the push that makes electricity move. It is measured between two points, such as the two terminals of a power supply. Its unit is the volt (V). A control panel often has 24 V DC for sensors and 120 V AC for relay coils.
- Current is how much electricity flows through a wire. Its unit is the ampere, or amp (A). Current flows only when there is a complete path, a circuit, from one side of the supply, through the load, and back to the other side.
- Resistance is how hard a part makes it for current to pass. Its unit is the ohm (Ω). A thick copper wire has almost none; a lamp or a relay coil (the electromagnet that closes a switch called a relay; module 3 shows how it works) has some; a dry plastic insulator has so much that almost no current passes.
A water pipe is a rough picture: voltage is the pressure, current is the flow, and resistance is how narrow the pipe is.
Ohm's law
The three are linked by Ohm's law:
V = I × R
Here V is voltage in volts, I is current in amps, and R is resistance in ohms. Knowing any two, you can find the third:
- I = V / R
- R = V / I
Units and prefixes
Control circuits use small currents and large resistances, so the numbers carry prefixes:
| Prefix | Means | Example |
|---|---|---|
| m (milli) | one thousandth | 100 mA = 0.1 A |
| k (kilo) | one thousand | 2.4 kΩ = 2400 Ω |
| M (mega) | one million | 1 MΩ = 1 000 000 Ω |
Change to plain volts, amps and ohms before you use Ohm's law, then change back.
Worked example: a relay coil
A relay coil rated 24 V DC has a resistance of 480 Ω. How much current does it draw?
I = V / R = 24 V / 480 Ω = 0.05 A = 50 mA.
A PLC output can supply only so much current (the data sheet says how much; 0.5 A per point is common for a 24 V DC output). 50 mA is well inside that, so the PLC can drive this coil directly.
Power
Power is how fast energy is used, in watts (W): P = V × I. The coil above uses 24 V × 0.05 A = 1.2 W. A 24 V DC pilot light that draws 25 mA uses 24 V × 0.025 A = 0.6 W. Adding up the watts of everything on a power supply tells you whether the supply is big enough.
Open and short circuits
Two faults are worth naming now, because you will meet them again when you find faults:
- An open circuit is a break in the path: a cut wire, a loose terminal, a switch that does not close. No current flows, and the load gets no voltage. If the wire to a PLC input is broken, that input reads FALSE all the time, whatever the button or sensor does.
- A short circuit is a path with almost no resistance, where there should be a load. By Ohm's law, a tiny R makes a huge I. Fuses and circuit breakers are there to open the circuit before the wires overheat. A shorted switch makes its input read TRUE all the time.
Try it
Open the Exercise tab and answer its practice questions: Ohm's law with real panel numbers, prefixes, and what an open wire does to an input. A wrong answer shows the right one and why. The Reference tab has Ohm's law on one page.
The questions (on the Exercise tab)
5 questions; the learner needs 80 % to pass and can try again. Practice: a wrong answer shows the right one. The right answers are marked ✓ here only.
Match each one. Match each quantity to its unit.
Voltage→ Volt (V)Current→ Ampere (A)Resistance→ Ohm (Ω)Power→ Watt (W)
Why: Voltage is the push (volts), current the flow (amps), resistance how hard it is to pass (ohms), and power how fast energy is used (watts).
A number. A relay coil rated 24 V DC has a resistance of 1.2 kΩ. How much current does it draw, in milliamps?
✓ 20 mA (within 0.5)
Why: 1.2 kΩ = 1200 Ω. I = V / R = 24 V / 1200 Ω = 0.02 A = 20 mA.
A number. A 24 V DC pilot light draws 50 mA. What is its resistance, in ohms?
✓ 480 Ω (within 5)
Why: 50 mA = 0.05 A. R = V / I = 24 V / 0.05 A = 480 Ω.
A number. A 120 V AC contactor coil draws 0.25 A. How much power does it use, in watts?
✓ 30 W (within 0.5)
Why: P = V × I = 120 V × 0.25 A = 30 W.
Choose one. The wire from a proximity sensor to a PLC input is cut. What does the PLC input read?
- ✓ FALSE all the time, whatever the sensor does
- TRUE all the time, whatever the sensor does
- The same as before: the PLC remembers the last value
- It switches between TRUE and FALSE
Why: A cut wire is an open circuit: no current reaches the input, so it reads FALSE. A short would make it read TRUE.
Your comments on this item
1.2 Series and parallel circuits
about 30 minutes · builds on 1.1
- Example
- None: this item has no machine.
- Exercise
- Practice questions (below). Passing them completes the item.
- Reference
- AND and OR with contacts, Ohm's law and power
The Learn tab
Series and parallel circuits
Parts in a circuit can be joined in two basic ways. Which way they are joined decides how the current and the voltage are shared, and, for switches, what logic they make.
Series: one path
Parts are in series when they are joined end to end, so there is only one path for the current. The same current flows through every part.
- Current: the same everywhere in the loop.
- Voltage: shared. The voltages across the parts add up to the supply voltage.
- Resistance: the total is the sum: R = R1 + R2 + …
- A break anywhere stops the current everywhere. Open one part and the whole loop goes dead.
Worked example
Two resistors, 200 Ω and 400 Ω, are in series across a 24 V DC supply.
- Total resistance: 200 Ω + 400 Ω = 600 Ω.
- Current: I = 24 V / 600 Ω = 0.04 A = 40 mA, through both.
- Voltage across the 200 Ω: 0.04 A × 200 Ω = 8 V. Across the 400 Ω: 0.04 A × 400 Ω = 16 V. Check: 8 V + 16 V = 24 V.
Parallel: several paths
Parts are in parallel when each one is joined straight across the same two points, so each has its own path. This is how a panel is wired: every pilot light, coil and sensor connects between the + and − of the 24 V DC supply (or the two wires of 120 V AC).
- Voltage: the same across every branch: each gets the full supply voltage.
- Current: each branch draws its own current, and the supply provides the total: I = I1 + I2 + …
- Resistance: the total is less than the smallest branch. For two branches, R = (R1 × R2) / (R1 + R2).
- A break in one branch turns off only that branch; the others keep working.
Worked example
Three 24 V DC pilot lights are wired in parallel. Each draws 25 mA. A relay coil of 480 Ω is also across the same supply.
- Each light gets 24 V and draws 25 mA: 3 × 25 mA = 75 mA.
- The coil draws 24 V / 480 Ω = 50 mA.
- The supply provides 75 mA + 50 mA = 125 mA in total.
Side by side
| Series | Parallel | |
|---|---|---|
| Paths for current | One | One per branch |
| Current | Same through every part | Adds up across branches |
| Voltage | Shared between parts | Same across every branch |
| Total resistance | Sum of the parts | Less than the smallest branch |
| One part opens | Everything stops | Only that branch stops |
Switches in series make AND
Wire two switches, A and B, in series with a lamp. The lamp lights only if A and B are both closed: one open switch breaks the only path. Write closed as TRUE and lit as TRUE:
Truth table: A AND B
| A | B | A AND B |
|---|---|---|
| FALSE | FALSE | FALSE |
| FALSE | TRUE | FALSE |
| TRUE | FALSE | FALSE |
| TRUE | TRUE | TRUE ✓ |
A two-hand start on a press works this way: the operator must press both buttons, so both hands are clear of the tool.
Switches in parallel make OR
Wire A and B in parallel, then to the lamp. The lamp lights if A or B (or both) is closed: either one gives the current a path.
Truth table: A OR B
| A | B | A OR B |
|---|---|---|
| FALSE | FALSE | FALSE |
| FALSE | TRUE | TRUE ✓ |
| TRUE | FALSE | TRUE ✓ |
| TRUE | TRUE | TRUE ✓ |
Two Start buttons, one at each end of a conveyor, are wired this way.
This is the bridge to ladder logic. In a ladder program, contacts in series are AND and contacts side by side are OR, exactly as the switches here. You will meet that again in modules 2 and 3.
Try it
Open the Exercise tab and answer its practice questions: a series total, a parallel current, and the truth table for switches in series. The Reference tab has AND and OR with contacts, and Ohm's law, on one page each.
The questions (on the Exercise tab)
4 questions; the learner needs 80 % to pass and can try again. Practice: a wrong answer shows the right one. The right answers are marked ✓ here only.
A number. A 100 Ω and a 500 Ω resistor are in series across 24 V DC. How much current flows, in milliamps?
✓ 40 mA (within 0.5)
Why: In series the resistances add: 100 Ω + 500 Ω = 600 Ω. I = 24 V / 600 Ω = 0.04 A = 40 mA.
A number. Four pilot lights are wired in parallel across a 24 V DC supply. Each draws 30 mA. How much current does the supply provide, in milliamps?
✓ 120 mA (within 1)
Why: In parallel each branch draws its own current, and the currents add: 4 × 30 mA = 120 mA.
Choose every one that is right. Which of these are true of parts wired in parallel? Choose every one that is.
- ✓ Each part has the full supply voltage across it
- The same current flows through every part
- ✓ If one part opens, the others keep working
- The total resistance is the sum of the parts
Why: Parallel branches share the voltage, not the current: each gets the full supply, and each has its own path, so one opening leaves the rest working. Same current and resistances adding are true of series.
Fill in a truth table. Two switches, A and B, are wired in series with a lamp. Fill in when the lamp is lit (TRUE = closed, or lit).
Truth table: A AND B
A B A AND B FALSE FALSE FALSE FALSE TRUE FALSE TRUE FALSE FALSE TRUE TRUE TRUE ✓ Why: In series there is one path: the lamp is lit only when A and B are both closed.
Your comments on this item
1.3 AC and DC in a control panel
about 30 minutes · builds on 1.2
- Example
- None: this item has no machine.
- Exercise
- Practice questions (below). Passing them completes the item.
- Reference
- AC and DC in a panel
The Learn tab
AC and DC in a control panel
Open a control panel and you will usually find three kinds of power side by side. Knowing which is which tells you what each wire does and how dangerous it is.
Direct and alternating current
- Direct current (DC) flows one way only. Its voltage is steady, and its two terminals are marked + and − (the − side is often called common or 0 V). Batteries and power supplies give DC.
- Alternating current (AC) changes direction many times a second. Its voltage rises, falls through zero, reverses and comes back, over and over. The power from the utility is AC, because AC is easy to step up and down with a transformer.
How often AC repeats is its frequency, measured in hertz (Hz): cycles per second. In the United States it is 60 Hz; in much of the rest of the world it is 50 Hz. A motor or coil made for one may not work properly on the other, which is why the nameplate lists it.
The three kinds of power in a panel
| Power | Typical use | Where it comes from |
|---|---|---|
| 480 V AC, three-phase | Motors, heaters | The building's supply, through a disconnect |
| 120 V AC, single-phase | Contactor and relay coils, the 24 V DC supply, lights, outlets | A control transformer that steps 480 V down to 120 V |
| 24 V DC | PLC inputs and outputs, sensors, pilot lights, small relays | A DC power supply that turns 120 V AC into 24 V DC |
Not every panel uses exactly these numbers (208 V and 240 V three-phase are common too), but the pattern is the same: high voltage for the work, low voltage for the control.
Three-phase power for motors
Large motors use three-phase power: three AC wires (often labeled L1, L2, L3), each reaching its peak a third of a cycle after the one before. Three-phase turns a motor smoothly and needs less copper for the same power than single-phase. A 480 V three-phase motor connects to all three lines through the main contacts of its contactor (a heavy-duty switch closed by an electromagnet, its coil; module 3 shows how it works). The PLC never switches 480 V itself: it switches the contactor's coil, and the contactor switches the motor.
Why control runs at a lower voltage
The circuits a person touches and works on most, the buttons, sensors and PLC wiring, run at 120 V AC or, more and more, 24 V DC, because:
- a lower voltage is far less likely to give a dangerous shock;
- small wires, buttons and sensors are cheaper and easier to fit;
- a fault in the control wiring does not put full motor voltage on the buttons.
Low voltage is less dangerous, not harmless. Treat every circuit as live until you have proved it is not (the next item).
AC and DC on the PLC
PLC input and output cards are made for one kind of power. A 24 V DC input card must not be wired to 120 V AC: it can be destroyed. Read the card's label before wiring it. The PLC's own power and the I/O power may also be different: a PLC can run on 120 V AC and still have 24 V DC inputs.
Reading a nameplate
Every motor, transformer and power supply has a nameplate with its ratings. On a motor, look for:
- V: the voltage it is wound for, such as 460 V (a 460 V motor runs on a 480 V supply);
- Ph: phases, 1 or 3;
- Hz: 60;
- FLA: full-load amps, the current it draws at full load, used to size its overload protection;
- HP and RPM: its power and speed.
A 24 V DC power supply's nameplate gives its output current, such as 5 A. Add up the current of everything on it (as in the last item) to make sure it is enough.
Try it
Open the Exercise tab and answer its practice questions: match each kind of power to its use, and read a frequency and a nameplate. The Reference tab has AC and DC in a panel on one page.
The questions (on the Exercise tab)
5 questions; the learner needs 80 % to pass and can try again. Practice: a wrong answer shows the right one. The right answers are marked ✓ here only.
Match each one. Match each kind of power to its usual job in a control panel.
480 V AC three-phase→ Runs the motors120 V AC→ Contactor coils and the DC power supply24 V DC→ PLC inputs, sensors and pilot lights
Why: High voltage does the work (motors); a control transformer gives 120 V AC for coils; a DC supply gives 24 V DC for the PLC's I/O and sensors.
A number. What is the frequency of AC mains power in the United States, in hertz?
✓ 60 Hz (within 0)
Why: US mains power is 60 Hz: 60 cycles a second. Much of the rest of the world uses 50 Hz.
Choose one. What does a control transformer in a panel do?
- ✓ Steps the high supply voltage down to 120 V AC for the control circuit
- Turns AC into 24 V DC
- Starts and stops the motor
- Changes 60 Hz into 50 Hz
Why: A transformer changes AC voltage: here, 480 V down to 120 V for coils and lights. Turning AC into DC is the job of a DC power supply.
Choose one. On a motor's nameplate, what does FLA tell you?
- ✓ The current it draws at full load
- The voltage it is wound for
- Its speed at full load
- How many phases it needs
Why: FLA is full-load amps: the current at full load, used to size the motor's overload protection.
Choose one. Why does the control circuit run at 24 V DC or 120 V AC rather than the motor's 480 V?
- ✓ It is much less likely to give a dangerous shock, and the parts are smaller and cheaper
- A PLC cannot count above 120
- Low voltage is completely safe to touch
- Motors need low voltage to start
Why: Lower control voltage reduces the shock risk and lets buttons, sensors and wiring be small. It is less dangerous, not harmless.
Your comments on this item
1.4 Working safely: lockout/tagout
about 30 minutes · builds on 1.3
- Example
- None: this item has no machine.
- Exercise
- Practice questions (below). Passing them completes the item.
- Reference
- Lockout/tagout
The Learn tab
Working safely: lockout/tagout
This page is an introduction only. It does not replace the safety training your lab or your employer gives you, and it does not qualify you to work on live equipment. Follow their procedures and your instructor's directions every time.
The hazards
Electricity in a panel can hurt you in three main ways:
- Shock: current passes through your body. About 50 mA (0.05 A, the current of the relay coil in item 1.1) crossing the chest can stop the heart, and 120 V can easily push that much through a person.
- Arc flash: a fault makes current jump through the air as a blast of light, heat and pressure. It can burn, blind and throw a person, even someone standing in front of the panel without touching anything.
- Burns: from the arc, from hot parts, or from current through the skin.
A machine adds its own hazards: a motor that starts while your hand is in a conveyor, air or hydraulic pressure, a raised load that falls, a spring that releases. These are why the whole machine, not just its wiring, must be made safe.
The rules that apply
Two documents set the rules in US workplaces:
- NFPA 70E, Standard for Electrical Safety in the Workplace: how to judge shock and arc-flash risk, who is qualified to work near live parts, and what protective equipment they wear.
- OSHA 29 CFR 1910.147, The control of hazardous energy (lockout/tagout): the federal regulation that requires an employer to have a written lockout/tagout program, train workers in it, and use it whenever someone services or maintains a machine where an unexpected start-up or release of energy could injure them.
Lockout/tagout
Lockout/tagout (LOTO) makes sure a machine cannot start, or release stored energy, while someone is working on it. Each worker puts their own lock on the energy-isolating device, such as a disconnect switch, and keeps the only key. A tag with their name says who locked it and why. The machine cannot be turned on until every lock is removed.
The steps, in order:
- Prepare and notify. Know every energy source of this machine (the machine's written procedure lists them). Tell the operators and anyone else affected that it is being shut down and locked out.
- Shut down the machine the normal way, with its Stop controls.
- Isolate it from every energy source: open the disconnect, close the air or hydraulic valves.
- Apply your lock and tag to each isolating device.
- Release or block stored energy: bleed air and hydraulic pressure, block parts that could fall or move, and let capacitors discharge.
- Verify zero energy. Try the normal Start, with everyone clear, and check that nothing moves; then return the control to off. Test for voltage with a meter, using live-dead-live: test the meter on a known live source, test the circuit (it must read dead), then test the meter on the live source again. The last test proves the meter did not fail during the check.
Only when the verify step shows zero energy is the machine safe to work on. Removing the locks has its own steps, also set by the procedure: tools and guards back, everyone clear and told, and each person removes only their own lock.
Things that are not a lockout
- An emergency stop is not a lockout. An e-stop stops the machine, but it is a control: a fault, a reset or another person can start the machine again. Never rely on it to keep you safe while you work.
- A PLC output turned off, a program stopped, or a stop button pressed is not isolation either. The power is still in the panel.
- A tag on its own is a warning, not a barrier. Use a lock wherever the device can take one.
Live work
Never open or work in a live panel unless you are qualified, have been trained for that task, are permitted by your employer or instructor, and wear the protective equipment the task calls for. In PLC+ you never need to: the machines are simulated. In the lab, your instructor decides what may be done with power on.
Try it
Open the Exercise tab and answer its practice questions: the LOTO steps in order, live-dead-live, and what an e-stop does and does not do. The Reference tab has the lockout/tagout steps on one page.
The questions (on the Exercise tab)
5 questions; the learner needs 80 % to pass and can try again. Practice: a wrong answer shows the right one. The right answers are marked ✓ here only.
Match each one. Put the lockout/tagout steps in order: match each step number to its step.
Step 1→ Prepare and notify the people affectedStep 2→ Shut the machine down with its normal controlsStep 3→ Isolate it from every energy sourceStep 4→ Apply your own lock and tagStep 5→ Release or block stored energyStep 6→ Verify zero energy
Why: Prepare and notify, shut down, isolate, lock and tag, release stored energy, then verify zero energy before you start work.
Choose one. Why is an emergency stop not a lockout?
- ✓ It is a control: a reset, a fault or another person can start the machine again
- It takes too long to press
- It only works on DC machines
- It turns off the lights as well
Why: An e-stop stops the machine but does not isolate it from its energy. Only a lock on the isolating device, with your key, keeps it from starting.
Choose one. When you check for voltage with a meter, why do you test the meter on a known live source again after testing the circuit?
- ✓ To prove the meter did not fail during the check, so its "dead" reading can be trusted
- To discharge the meter
- Because the first test is only for AC
- To reset the circuit breaker
Why: Live-dead-live: if the meter fails, it reads "dead" on a live circuit. Testing it on a live source before and after proves it was working.
Choose every one that is right. Which of these can injure you at an electrical panel? Choose every one that is.
- ✓ Shock from touching a live part
- ✓ Arc flash, even without touching anything
- ✓ Burns
- Nothing, once the PLC program is stopped
Why: Shock, arc flash and burns are the main electrical hazards. Stopping the PLC program does not remove power from the panel.
Choose one. Which OSHA regulation requires lockout/tagout when servicing machines?
- ✓ 29 CFR 1910.147, the control of hazardous energy
- NFPA 70E
- IEC 61131-3
- The motor's nameplate
Why: OSHA 29 CFR 1910.147 is the lockout/tagout regulation. NFPA 70E is the electrical safety standard (a standard, not an OSHA regulation), and IEC 61131-3 is the PLC programming standard.
Your comments on this item
1.5 Module check
about 15 minutes
- Module check
- Complete when every item it covers is: 1.1, 1.2, 1.3, 1.4. Its questions, on the Exercise tab, are below; it is complete when those items are and the questions are passed. Once it is complete, the learner makes the PDF progress report to hand in (Hand in a report).
The Learn tab
Module check: electrical foundations
This check covers the four items of module 1. Each of them is complete once you have passed its practice questions on its Exercise tab.
The check itself is ten questions, on the Exercise tab: choices, numbers worked out with Ohm's law, matching the parts of a panel to their power, and a truth table. You need 80 % to pass, and you can try again as often as you like. A right answer says why; a wrong one tells you to look again, not what the answer is. Keep a calculator to hand.
When the four items are complete and you have passed the questions, the module is complete and ready to hand in: Hand in a report (the second row of the path) makes the PDF progress report for your instructor.
The questions (on the Exercise tab)
10 questions; the learner needs 80 % to pass and can try again. A wrong answer says “not quite, look again”; the reason is shown once the answer is right. The right answers are marked ✓ here only.
A number. A 24 V DC relay coil has a resistance of 600 Ω. How much current does it draw, in milliamps?
✓ 40 mA (within 0.5)
Why: Ohm's law: I = V / R = 24 V / 600 Ω = 0.04 A, which is 40 mA.
A number. A 24 V DC power supply feeds loads that draw 2.5 A in total. How much power is it delivering, in watts?
✓ 60 W (within 0.5)
Why: P = V × I = 24 V × 2.5 A = 60 W.
Choose one. The two wires to a limit switch touch each other where the insulation has worn through, so the switch is bypassed. What does its PLC input read?
- ✓ TRUE all the time, whatever the switch does
- FALSE all the time, whatever the switch does
- It still follows the switch
- The input card turns itself off
Why: The wires touching are a short across the switch: the input always has voltage, so it reads TRUE. A broken wire (an open) would read FALSE.
A number. A 300 Ω and a 900 Ω resistor are in series across 24 V DC. What is the voltage across the 900 Ω resistor, in volts?
✓ 18 V (within 0.2)
Why: Total R = 300 Ω + 900 Ω = 1200 Ω, so I = 24 V / 1200 Ω = 0.02 A. Across the 900 Ω: 0.02 A × 900 Ω = 18 V (and 6 V across the 300 Ω; 18 V + 6 V = 24 V).
Fill in a truth table. Two Start buttons, A and B, are wired in parallel to a lamp. Fill in when the lamp is lit (TRUE = pressed, or lit).
Truth table: A OR B
A B A OR B FALSE FALSE FALSE FALSE TRUE TRUE ✓ TRUE FALSE TRUE ✓ TRUE TRUE TRUE ✓ Why: In parallel either button gives the current a path, so the lamp is lit when A or B (or both) is pressed.
Choose one. Six pilot lights are wired in parallel across 24 V DC. One lamp burns out (it opens). What happens to the other five?
- ✓ They stay lit: each has its own path
- They all go out
- They get brighter, because they share its voltage
- They flicker
Why: Each parallel branch has its own path and the full 24 V, so one opening leaves the others working. In series they would all go out.
Match each one. Match each part of a control panel to the power that comes out of it.
Main disconnect→ 480 V AC three-phase for the motorsControl transformer→ 120 V AC for coils and lightsDC power supply→ 24 V DC for PLC I/O and sensors
Why: The disconnect brings in the building's three-phase power; the control transformer steps it down to 120 V AC; the DC supply turns 120 V AC into 24 V DC.
Choose one. A PLC input card is labeled 24 V DC. A technician wants to wire a 120 V AC button circuit to it. What is right?
- ✓ Don't: a 24 V DC input card must not be wired to 120 V AC; it can be destroyed
- It is fine: the card will read it as TRUE
- It is fine if the button is normally closed
- It is fine at 60 Hz but not at 50 Hz
Why: I/O cards are made for one kind of power. Read the label before wiring: 120 V AC on a 24 V DC input can destroy it.
Choose one. You have opened the disconnect, put your lock and tag on it, and bled the air pressure. What comes next, before you start work?
- ✓ Verify zero energy: try the Start with everyone clear, and test for voltage with a meter, live-dead-live
- Press the emergency stop to be sure
- Start work: the lock makes it safe
- Hand the key to the operator
Why: The last step of lockout/tagout is to verify zero energy. Only then is it safe to work. You keep your own key.
Choose every one that is right. Which of these keep a machine safe to work on? Choose every one that does.
- ✓ Your own lock on the disconnect, with your own key
- The emergency stop pressed in
- The PLC program stopped
- ✓ Stored energy released or blocked, and zero energy verified
Why: An e-stop and a stopped program are controls, not isolation: the machine can still be started and the panel is still live. Lockout with your own lock, stored energy released, and zero energy verified make it safe.