Surface discharge filter with B&G CTS24 for an impaired water

A 1.0-inch treatment depth through B&G CTS24; Impaired Water, Zone 3.

1The problem

A 3-acre commercial site discharging to an impaired water filters 1.0 in of runoff through B&G CTS24 media.

InputValueSource
Project (General Site Information)
Meteorological zoneFlorida Zone 3Zone map (help page 815)
Mean annual rainfall54 inMean annual rainfall map (help page 815)
Performance standard (analysis type)Impaired WaterSite (illustrative)
Catchment 1: Commercial site (Watershed Characteristics)
Land use, pre / postUndeveloped - Mesic Flatwoods / High-Intensity CommercialSite (illustrative)
Area, pre / post3 / 3 acSite (illustrative)
Non-DCIA curve number, pre / post70 / 80Site (illustrative)
DCIA, pre / post0 / 70 %Site (illustrative)
EMC TN, pre / post1.087 / 2.400 mg/LBMPFast land use table (AH Vol I Table 9.2)
EMC TP, pre / post0.043 / 0.345 mg/LBMPFast land use table (AH Vol I Table 9.2)
Media mixB&G CTS24 (TN 75 %, TP 95 %)BMPFast media table (help page 817)
Filtration System (worksheet)
Treatment Depth1.0 inDesign (illustrative)

Find: the TN and TP removal of the BMP, the loads leaving the site, and whether the performance standard is met.

2Steps in BMPFast

  1. Press New Project. On General Site Information (the main window; its title bar reads General Site Information and your license key) type the project name Surface discharge filter: B&G CTS24, impaired water, choose Florida Zone 3, enter 54 in of mean annual rainfall and choose the performance standard Impaired Water.

    General Site Information (the main window).
    General Site Information (the main window).
  2. Press 1. Enter Catchment. For Catchment 1 type the name Commercial site, choose the land uses Undeveloped - Mesic Flatwoods (pre) and High-Intensity Commercial (post), enter the areas 3 and 3 ac, the non-DCIA curve numbers 70 and 80 and the DCIA 0 and 70 %, then press Calculate. BMPFast shows the annual runoff coefficient, the runoff and the TN and TP loads. Press Back.

    Watershed Characteristics Worksheet (1. Enter Catchment).
    Watershed Characteristics Worksheet (1. Enter Catchment).
  3. Press 2. Enter Treatment, then Surface Discharge Filter, and on its worksheet press Media. Choose B&G CTS24 (TN 75 %, TP 95 % when all the runoff is treated) and press Back.

    Enter Media Mix Information (the Media button).
    Enter Media Mix Information (the Media button).
  4. Press 2. Enter Treatment and then Surface Discharge Filter. On the Filtration System worksheet: Treatment Depth 1.0 in. Press Calculate. The report on the worksheet shows the inputs and the results.

    The BMP worksheet after Calculate: the report on the left.
    The BMP worksheet after Calculate: the report on the left.
  5. Press the same button again, now labelled Equations: the worksheet shows each equation with this problem’s values. Press Back to return to the treatment options.

    The same worksheet showing Equations: each equation with this problem’s values.
    The same worksheet showing Equations: each equation with this problem’s values.
  6. On the main window press 3. Configure Catchments and double-click Catchment 1. Choose Filtration as the BMP used in routing and the Outlet as where it goes. Press Back twice. (A catchment’s BMP is only used once it is chosen here.)

    Routing for Catchment 1 (3. Configure Catchments): the BMP used and where the catchment goes.
    Routing for Catchment 1 (3. Configure Catchments): the BMP used and where the catchment goes.
  7. Press 4. Summary Report. The Report Viewer shows the loads, the removal and whether the performance standard is met. Press Save Project to keep your copy; compare it with the .bmpt under Files.

    The Summary Report (4. Summary Report) in the Report Viewer.
    The Summary Report (4. Summary Report) in the Report Viewer.

3Results

ResultValue
Catchment 1: computed by BMPFast
Annual runoff coefficient (ROC), pre / post0.078 / 0.596
Runoff, pre / post1.053 / 8.046 ac-ft/yr
TN load, pre / post1.411 / 23.810 kg/yr
TP load, pre / post0.056 / 3.423 kg/yr
Filtration: computed by BMPFast
Treatment depth1.000 in
Hydraulic capture efficiency71.10 %
Provided TN / TP removal53.33 % / 67.54 %
TN load in → out23.810 → 11.113 kg/yr
TP load in → out3.423 → 1.111 kg/yr
Site (all catchments, at the outlet)
TN load: catchments → outlet23.810 → 11.113 kg/yr
TP load: catchments → outlet3.423 → 1.111 kg/yr
Provided removal TN / TP53.3 % / 67.5 %
Required removal TN / TP (Maximum % Removal)94.1 % (not met) / 98.4 % (not met)

The BMP report

Open this report on its own page.

The Summary Report

Open this report on its own page.

4Check

Runoff and loads (Equations 9-1 and 9-2 of AH Vol I).

1.233 kg is 1 mg/L in 1 ac-ft.

Capture. The retention efficiency tables for Florida Zone 3 at a treatment depth of 1.000 in, non-DCIA CN 80.00 and DCIA 70.0 % give a hydraulic capture of 71.10 % (AH Vol I Appendix O; read the same tables with Tools › Retention Efficiency Lookup Tables, help page 4325).

Removal.

The water captured passes through the media and leaves as surface discharge, so removal = capture × media reduction:

The media reductions are those of B&G CTS24 (Media and Filtration Methodology).

Load out.

The standard is not met, and that is expected. “Impaired Water” requires 80 % TN and 80 % TP, and the post-development load not above the pre-development load, for a discharge to an impaired water (AH Vol I 8.3.4(a)). The post = pre removal (Equation 9-3, (post load − pre load) / post load) is TN 94.1 % and TP 98.4 %. BMPFast takes the larger of the standard’s percentage and the post = pre removal as the Maximum % Removal, shown on every worksheet’s status bar and in the Summary Report: here TN 94.1 % and TP 98.4 %. This problem shows what this design removes (53.3 % / 67.5 %), which is less. To meet it, add BMPs in series or downstream catchments (see BMPs in Series and Routing), or size the BMP (see Sizing).